Moxa 85M-2600-T
85M-2600-T
ioPAC 8500 Series (85M) Modules
Module for the ioPAC 8500/8600 Series, 16 DOs, 24 VDC sink, -40 to 75°C operating temperature
Input/Output Interface
Digital Output Channels
- 16
Isolation
- 3k VDC or 2k Vrms
Digital Outputs
Voltage
- 24 VDC
Connector
- Spring-type Euroblock terminal
Current Rating
- 200 mA per channel
I/O Mode
- DO or PWM
I/O Type
- Sink
Over-Current Protection
- 0.65 A per channel @ 25°C
Over-Temperature Shutdown
- 175°C (typical), 150°C (min.)
Pulse Output Frequency
- 5 kHz
Over-Voltage Protection
- 45 VDC (typical)
Power Parameters
Power Consumption
- 35.4 mA @ 24 VDC
Physical Characteristics
Dimensions
- 25 x 128.2 x 85.5 mm (0.98 x 5.05 x 3.37 in)
Weight
- Under 80 g
Wiring
- I/O cable, 14 to 28 AWG
Environmental Limits
Operating Temperature
- -40 to 75°C (-40 to 167°F)
Storage Temperature (package included)
- -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity
- 5 to 95% (non-condensing)
Altitude
- 2000 m
Note: Please contact Moxa if you require products guaranteed to function properly at higher altitudes.
- 2000 m
Standards and Certifications
EMC
- EN 55032/24
EN 61000-6-2/-6-4
- EN 55032/24
EMI
- CISPR 32, FCC Part 15B Class A
EMS
- IEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV
IEC 61000-4-3 RS: 5100 MHz to 6000 MHz: 3 V/m
IEC 61000-4-4 EFT: Power: 1 kV; Signal: 0.5 kV
IEC 61000-4-5 Surge: Power: 2 kV; Signal: 1 kV
IEC 61000-4-6 CS: 10 V
IEC 61000-4-8 PFMF
- IEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV
Railway
- EN 50121-4
EN 50155 (complies with a portion of EN 50155 specifications)
- EN 50121-4
Safety
- UL 508
Shock
- IEC 60068-2-27
Vibration
- IEC 60068-2-6
MTBF
Time
- 792,571 hrs
Standards
- Telcordia SR332
Warranty
Warranty Period
- 5 years
Details