Moxa 86M-1620D-T
86M-1620D-T
ioPAC 8600 Series (86M) Modules
Module for the ioPAC 8600 Series, 16 DIs, 24 to 110 VDC, sink, channel LED, -40 to 75°C operating temperature
Input/Output Interface
Digital Input Channels
- 16
Isolation
- 3k VDC or 2k Vrms
Digital Inputs
Connector
- Spring-type Euroblock terminal
Voltage
- 24 to 110 VDC
Debouncing Function
- Software enable/disable
Debouncing Time
- 1 to 15 ms (software-selectable)
I/O Mode
- DI
Points per COM
- 8 channels
Scan on Time
- 0.5 ms
Scan Period
- 8 ms (typical)
Sensor Type
- PNP
Wet Contact (DI to COM)
- On: > 0.3 times external power voltage
Off: < 0.15 times external power voltage
- On: > 0.3 times external power voltage
Digital Outputs
Connector
- Spring-type Euroblock terminal
I/O Mode
- DO or PWM
Power Parameters
Power Consumption
- 12.6 mA @ 24 VDC
Physical Characteristics
Dimensions
- 25 x 128.2 x 85.5 mm (0.98 x 5.05 x 3.37 in)
Weight
- Under 80 g
Wiring
- I/O cable, 16 to 28 AWG
Environmental Limits
Operating Temperature
- -40 to 75°C (-40 to 167°F)
Storage Temperature (package included)
- -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity
- 5 to 95% (non-condensing)
Altitude
- 2000 m Please contact Moxa if you require products guaranteed to function properly at higher altitudes.
Standards and Certifications
EMC
- EN 55032/24, EN 61000-6-2/-6-4
EMI
- CISPR 32, FCC Part 15B Class A
EMS
- IEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV
IEC 61000-4-3 RS: 5100 MHz to 6000 MHz: 3 V/m
IEC 61000-4-4 EFT: Power: 1 kV; Signal: 0.5 kV
IEC 61000-4-5 Surge: Power: 2 kV; Signal: 1 kV
IEC 61000-4-6 CS: 10 V
IEC 61000-4-8 PFMF
- IEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV
Railway
- EN 50121-4, EN 50155
Safety
- UL 508
Shock
- IEC 60068-2-27
Vibration
- IEC 60068-2-6
MTBF
Time
- 1,115,244 hrs
Standards
- Telcordia SR332
Warranty
Warranty Period
- 5 years