Moxa ioLogik E2214
ioLogik E2214
ioLogik E2200 Series
Universal controller, 6 DIs, 6 relays, Click&Go, -10 to 60°C operating temperature
Control Logic
Language
- Click&Go
Input/Output Interface
Digital Input Channels
- 6
Relay Channels
- 6
Buttons
- Reset button
Isolation
- 3k VDC or 2k Vrms
Rotary Switch
- 0 to 9
Digital Inputs
Connector
- Screw-fastened Euroblock terminal
Counter Frequency
- 900 Hz
Digital Filtering Time Interval
- Software configurable
Dry Contact
- On: short to GND
Off: open
- On: short to GND
I/O Mode
- DI or event counter
Points per COM
- 3 channels
Sensor Type
- Dry contact
Wet Contact (NPN or PNP)
- Dry contact
Wet Contact (DI to GND)
- On: 0 to 3 VDC
Off: 10 to 30 VDC
- On: 0 to 3 VDC
Relays
Connector
- Screw-fastened Euroblock terminal
Contact Current Rating
- Inductive load: 2 A @ 30 VDC, 250 VAC, 110 VAC
Resistive load: 5 A @ 30 VDC, 250 VAC, 110 VAC
- Inductive load: 2 A @ 30 VDC, 250 VAC, 110 VAC
Contact Resistance
- 100 milli-ohms (max.)
Electrical Endurance
- 100,000 operations @ 5 A resistive load
Mechanical Endurance
- 1,000,000 operations
Minimum Permitted Load
- 1 A @ 5 VDC
Pulse Output Frequency
- 0.3 Hz at rated load
Type
- Form A (N.O.) power relay
I/O Mode
- Relay or pulse output
Note
- Ambient humidity must be non-condensing and remain between 5 and 95%. The relays may malfunction when operating in high condensation environments below 0°C.
LED Interface
LED Indicators
- PWR, RDY, Serial, I/O Status
Ethernet Interface
10/100BaseT(X) Ports (RJ45 connector)
- 1
Magnetic Isolation Protection
- 1.5 kV (built-in)
Ethernet Software Features
Configuration Options
- Web Console (HTTP)
Windows Utility (ioAdmin)
- Web Console (HTTP)
Industrial Protocols
- CGI commands
Modbus TCP Server (Slave)
Moxa AOPC (Active Tag)
MXIO Library
SNMPv1 Trap
SNMPv1/v2c/v3
- CGI commands
Management
- BOOTP
IPv4
SMTP
DHCP Client
HTTP
TCP/IP
- BOOTP
MIB
- Device Settings MIB
Time Management
- SNTP
Modbus TCP
Functions Supported
- 1, 2, 3, 4, 5, 6, 15, 16
Mode
- Server
Serial Interface
Connector
- Terminal block
Serial Standards
- RS-485
No. of Ports
- 1
Baudrate
- 1,200 bps to 115.2 kbps
Parity
- None
Data Bits
- 8
Stop Bits
- 1
Flow Control
- None
Serial Signals
RS-485-2w
- Data+, Data-, GND
Serial Software Features
Industrial Protocols
- Modbus RTU Server (Client)
Power Parameters
Power Connector
- Screw-fastened Euroblock terminal
No. of Power Inputs
- 1
Input Voltage
- 12 to 36 VDC
Power Consumption
- 170 mA @ 24 VDC
Physical Characteristics
Dimensions
- 115 x 79 x 45.6 mm (4.53 x 3.11 x 1.80 in)
Weight
- 250 g (0.55 lb)
Installation
- DIN-rail mounting
Wall mounting
- DIN-rail mounting
Wiring
- I/O cable, 16 to 26 AWG
Power cable, 16 to 26 AWG
- I/O cable, 16 to 26 AWG
Housing
- Plastic
Environmental Limits
Operating Temperature
- -10 to 60°C (14 to 140°F)
Storage Temperature (package included)
- -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity
- 5 to 95% (non-condensing)
Altitude
- 2000 m Please contact Moxa if you require products guaranteed to function properly at higher altitudes.
Standards and Certifications
Freefall
- IEC 60068-2-32
EMC
- EN 61000-6-2/-6-4
Safety
- UL 508
EMI
- CISPR 32, FCC Part 15B Class A
EMS
- IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV
IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m
IEC 61000-4-4 EFT: Power: 2 kV; Signal: 1 kV
IEC 61000-4-5 Surge: Power: 1 kV
IEC 61000-4-6 CS: 10 V
IEC 61000-4-8 PFMF
- IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV
Shock
- IEC 60068-2-27
Vibration
- IEC 60068-2-6
Declaration
Green Product
- RoHS, CRoHS, WEEE
MTBF
Time
- 307,239 hrs
Standards
- Telcordia SR332
Warranty
Warranty Period
- 2 years
Details